Key requirement

BS 5306-3 / BS 5306-8

Basic service

Annually

Extended service

Every 5 years

CO2 overhaul

Every 10 years

On this page
Talk to an engineer

01726 839333

Mon–Fri 8am–5pm. 24/7 emergency line out of hours.

01

Servicing

Extinguisher compliance fails in predictable ways: the wrong type next to the risk, units missing from their brackets, signage absent, and a service label three years out of date. None of it is difficult — it just needs a schedule and someone who owns it.

Recall surveys the building against BS 5306-8, supplies and installs the correct extinguisher types, and services them annually with tamper seals, pressure checks and a signed certificate covering every unit on site.

Every extinguisher is tagged and logged, so the annual visit knows exactly what should be present and immediately flags anything that has walked.

Annual basic service

Visual and mechanical checks, weight, pressure, seals, hoses and operating instructions.

Extended service

Five-yearly discharge test and refill for water-based units; ten-yearly CO2 overhaul.

02

Inspection Process

1

Provision survey

We identify the risks present and the extinguisher classes and travel distances required.

First visit

2

Supply and install

Correct units supplied, mounted at the right height, signed and tagged.

Same or next visit

3

Annual service

Every unit checked, sealed and labelled; missing or discharged units reported.

Every 12 months

4

Extended service & replacement

Five and ten-year work scheduled ahead so it never arrives as a surprise cost.

By unit age
03

Compliance

Provision survey

Building assessed against BS 5306-8 for extinguisher type, size, location and travel distance.

Signage and ID

Location signs, ID signs and a site plan showing where every unit lives.

Type
Fire classes
Typical location
Water / water additive
A
Corridors, offices, storerooms
Foam
A, B
Reception areas, workshops, fuel stores
CO2
B, electrical
Server rooms, plant rooms, near boards
Dry powder
A, B, C
External plant, vehicles, gas risks
Wet chemical
F
Commercial kitchens with deep fat frying

Powder is generally avoided indoors — the residue is highly disruptive and can be dangerous in confined escape routes.

The Regulatory Reform (Fire Safety) Order 2005 requires the responsible person to provide appropriate firefighting equipment and to maintain it in efficient working order and in good repair. BS 5306-3 sets the servicing regime; BS 5306-8 sets the provision and siting.
RRO 2005
BS 5306-3
BS 5306-8
BS EN 3
04

Maintenance Plans

Supply and installation

Water, foam, CO2, powder and wet chemical units supplied, bracketed and signed.

Certificate and asset log

Signed certificate plus a per-unit register with service and replacement dates.

05

Why choose Recall

Frequently asked

How many extinguishers do we need?

It is based on floor area, the classes of fire present and maximum travel distance — usually 30 metres to a Class A extinguisher. The provision survey works it out room by room.

A competent person can carry out monthly visual checks. The annual service must be done by a competent servicing technician, which is a specific qualification.

A deeper five-yearly service on water-based units: full discharge, internal inspection and refill. CO2 units instead get a ten-yearly pressure test overhaul.

In kitchens, yes — alongside a wet chemical extinguisher. We include blankets and signage in the provision survey where cooking risks exist.