Standard

BS 5839-9

Servicing

Twice yearly

Battery standby

24 hours minimum

Coverage

Every designated refuge

On this page
Talk to an engineer

01726 839333

Mon–Fri 8am–5pm. 24/7 emergency line out of hours.

01

Refuge Systems Overview

If your evacuation strategy relies on anyone waiting in a refuge — a protected lobby or stair landing — then that person needs to be able to talk to the people managing the evacuation. Waiting alone in a stairwell with no way to say where you are, and no confirmation anyone is coming, is not an evacuation plan.

Emergency voice communication systems provide exactly that: a call point at each refuge connected to a master panel at the fire panel or reception, with battery standby so it survives a mains failure.

Systems are designed to BS 5839-9, which covers refuge points, fire telephones, disabled toilet alarms and the master station. The design question is where refuges actually are in your evacuation strategy — and on a surprising number of sites that has never been formally decided.

We work from the fire strategy and the fire risk assessment. Each designated refuge gets a call point, each is labelled, and the master station clearly identifies which refuge is calling so a marshal is not guessing between floors.

Installation is usually straightforward retrofit — two-core fire-rated cable back to a master panel. Servicing is twice yearly, checking every outstation, the master, the battery standby and audibility at both ends.

Refuge call point in a protected stair lobby
02

Installation & Coverage

Strategy review

Designated refuges identified from the fire strategy and risk assessment.

Refuge call points

Type B outstations at each refuge, labelled and clearly identifiable at the master.

Fire telephones

Type A fire telephone outstations where the strategy requires them.

Master station

Panel sited at the fire alarm panel or reception with battery standby.

Disabled toilet alarms

Call systems and reset units, with signage and staff response guidance.

Twice-yearly servicing

Every outstation and the master tested, with certification issued.

03

Servicing

1

Review the strategy

We confirm where refuges are, or flag that they have never been designated.

Survey visit

2

Design and quote

Outstation schedule, cable routes, master station position and a fixed price.

Within 5 days

3

Install and commission

Fire-rated cabling, outstations fitted and labelled, audibility tested both ways.

1–3 days

4

Handover and training

Marshals shown how the master works and what to do when a refuge calls.

On completion

5

Servicing

Twice-yearly service added to your compliance calendar with certification.

Ongoing
04

Outstation types

Type
What it is
Where it goes
Type A
Fire telephone, handset in a cabinet
Firefighting shafts, fire service use
Type B
Refuge call point, hands-free
Refuge areas on escape routes
Type C
Steward or marshal phone
Assembly points, control positions
Disabled WC
Pull cord alarm and reset
Accessible toilets

Refuge points are Type B in almost all buildings. Type A fire telephones are for the fire service and are specified by the fire strategy, not by preference.

05

Your legal duty

The Regulatory Reform (Fire Safety) Order 2005 requires arrangements for the safe evacuation of all relevant persons, including those needing assistance. Where refuges form part of that strategy, BS 5839-9 governs the design, installation, commissioning and maintenance of the communication system.
RRO 2005
BS 5839-9
Approved Document B
Equality Act 2010
06

Why choose Recall

Frequently asked

Do we need a refuge system?

If your evacuation strategy uses refuges, yes. If it does not, the first question is whether it should — most multi-storey buildings with disabled access need a defined assisted evacuation route.

Yes. It is a separate two-core fire-rated system, so retrofit is usually simple and non-disruptive.

Whoever is coordinating the evacuation — normally the fire marshal at the panel or reception. Response procedure is part of handover training.

Twice a year, testing every outstation and the master station along with battery standby.