Dry riser test

Annual wet pressure test

Visual inspection

Every 6 months

Sprinkler service

Quarterly & annual

Standard

BS 9990 / BS EN 12845

On this page
Talk to an engineer

01726 839333

Mon–Fri 8am–5pm. 24/7 emergency line out of hours.

01

Systems Overview

Dry risers and sprinklers are not there for you — they are there for the fire service and for the building. A dry riser that fails a pressure test, or an inlet that has been vandalised or built over, removes the firefighting capability from a whole building.

These systems are also the easiest to forget, because nothing about them signals a problem. There is no panel showing a fault and no alarm when a valve is closed.

Dry risers require a visual inspection every six months and a full wet pressure test annually to BS 9990, run at 12 bar for 15 minutes with the outlets and inlet checked, and the results certified. We also check access: inlet cabinets that are locked with the wrong key, obstructed by parking or hidden behind planting are a real and common failure.

Sprinkler systems are maintained to BS EN 12845, which sets weekly, monthly, quarterly and annual regimes. We take the quarterly and annual work and set your on-site team up to do the weekly valve and gauge checks with a logbook that records them properly.

Findings arrive prioritised. A closed valve or a failed pressure test is immediate; a corroded outlet cap or missing signage goes on a schedule. Where remedial work is needed we price it against the same report.

Dry riser inlet inspection
02

Testing & Inspection

Dry riser wet test

Annual pressure test to BS 9990 with certification and photographic record.

Six-monthly inspection

Visual check of inlets, outlets, caps, valves, signage and access.

Sprinkler servicing

Quarterly and annual servicing to BS EN 12845, including valve and pump checks.

Pump testing

Fire pump run tests, alarm signalling checks and flow verification where fitted.

Remedial works

Caps, gaskets, valves, cabinet repairs and access reinstatement.

Logbook setup

Weekly and monthly checks documented so your team can run them correctly.

03

Maintenance

1

Asset survey

Risers, valves, inlets, outlets and pumps located and recorded per building.

First visit

2

Access check

We confirm the fire service can actually reach and use the inlet — often the real defect.

First visit

3

Test and certify

Pressure testing and servicing carried out, with certification issued.

On the visit

4

Remedials and schedule

Priced actions issued and the recurring test regime added to your calendar.

Within 10 days
04

Testing frequencies

System
Fire alarm
Lockdown alarm
Dry riser
6 monthly
Visual inspection of inlet, outlets, valves and access
Dry riser
Annually
Wet pressure test at 12 bar for 15 minutes, certified
Sprinkler
Weekly
Valve positions, gauge pressures, alarm test (site team)
Sprinkler
Quarterly & annually
Full service, pump tests and flow checks to BS EN 12845

Weekly sprinkler checks are usually done by a competent person on site — we supply the logbook and the training to do it properly.

05

Your legal duty

The Regulatory Reform (Fire Safety) Order 2005 requires firefighting equipment and facilities to be maintained in efficient working order and in good repair. Dry riser testing follows BS 9990 and sprinkler maintenance follows BS EN 12845; insurers frequently make both a policy condition.
RRO 2005
BS 9990
BS EN 12845
LPC Rules
06

Why choose Recall

Frequently asked

Does the wet test flood the building?

No. The riser is filled and pressurised under controlled conditions with the outlets managed, and drained down afterwards. We use hoses to a suitable discharge point.

Very common. Inlet cabinets should be secured with a fire service standard lock. We replace non-standard padlocks as part of remedials.

Your site team, using the logbook we set up. We cover the quarterly and annual work that needs specialist equipment.

Yes — for residential blocks and hotels that is usually preferable, since testing involves water and access to communal areas.